AIR CONDITIONING
Fully Air Conditioned - Total Calculated Load / Chiller Capacity
d Provided 2275 TR.
Designed for 65 sft. Per head - Against 80 to 100 sft. by
d Industry Average.
Number of Chillers : 8
Number of Primary Pumps : 8 Plus 3 Stand-by.
Number of Secondary Pumps : 6 Plus 3 Stand-by.
Number of AHUs per Floor : 12.
Designed for Inside Ambient Temperature of 22 Degrees -
d Against 24 to 26 Degrees celsius by Industry Average.
Distribution upto AHUs only. Air Conditioning Distribution into Office d d Areas from AHU rooms, Ducting, Branching, Diffusers etc.
d Not included.
The Air Handler Room is located near the periphery for the free flow
d of fresh air to air handler for effective dilution of return air, for better d indoor quality.
All AHU rooms are provided with two air handlers for taking
d advantage of variation of load in the space for power consumption
d and also for any burn out of fan motor. Atleast one unit can circulate d the air. Two way valves to be actuated by thermostat are provided
d for control of chilled water further in response to variation
d in inside load. |
|
|
|